Ten electrical parameter calculator works out the current a motor or machine draws and sizes the breaker, contactor and cable. Three-phase current I = P / (√3 × U × cos φ × η): a 7.5 kW motor at 400 V, PF 0.85 and 90% efficiency draws 14.2 A — use a 20 A breaker, an 18 A contactor and 2.5 mm² copper cable.

  • Free, no sign-up
  • Instant results
  • Shareable link

Enter your values

Power unit
Supply
Phase-to-phase for three-phase. Find your country’s voltage.
M
H
per kWh

Wyniki

Live
Full-load current14.2 Afull-load current · 3-phase 400 V
Apparent power
9.80 kVA
Input power
8.33 kW
Circuit breaker
20 A (motor-rated: up to 40 A)
Contactor (AC-3)
18 A AC-3
Copper cable
2.5 mm² Cu (≈ AWG 14)
Energy consumption
66.7 kWh

Cable size for copper, PVC insulation, in conduit (IEC method B2), 30 °C, three loaded conductors; derate for grouping, high temperature or long runs and follow local electrical code (IEC 60364 / NEC).

Motor current formulas

Three-phase: I = P × 1000 / (√3 × U × cos φ × η)
Single-phase: I = P × 1000 / (U × cos φ × η)
  • P rated mechanical (shaft) power in kW (1 hp = 0.7457 kW)
  • U supply voltage (phase-to-phase for three-phase)
  • cos φ power factor, typically 0.80–0.90
  • η motor efficiency, typically 0.85–0.96

The breaker is the next standard size above 125% of full-load current; motor-rated (inverse-time) breakers may be set up to 250% to ride through the starting current. The contactor is chosen by AC-3 rating ≥ full-load current, and the cable carries at least 125% of the current. Voltage drop is checked against 5%.

How to use the Electrical Parameter Calculator

  1. Wejdź power of the motor or machine (kW or hp).
  2. Wybierać three-phase or single-phase i voltage.
  3. Keep the typical power factor I efektywność or use nameplate values.
  4. Add cable length and operating hours for voltage drop and energy use.

Worked example

7.5 kW motor, 400 V three-phase, cos φ 0.85, η 0.90. Input power = 7.5 / 0.9 = 8.33 kW; apparent power = 8.33 / 0.85 = 9.80 kVA; I = 9,804 / (1.732 × 400) = 14.2 A. Breaker ≥ 1.25 × 14.2 = 17.7 A → 20 A; contactor 18 A; cable for 17.7 A → 2.5 mm² Cu. Eight hours of operation use about 66.7 kWh.

Typical full-load current of three-phase motors

cos φ 0.85, η 0.90.

Silnik230 V380 V400 V480 V
1.5 kW (2.0 hp)4.9 A3.0 A2.8 A2.4 A
2.2 kW (3.0 hp)7.2 A4.4 A4.2 A3.5 A
4 kW (5.4 hp)13.1 A7.9 A7.5 A6.3 A
5.5 kW (7.4 hp)18.0 A10.9 A10.4 A8.6 A
7.5 kW (10.1 hp)24.6 A14.9 A14.2 A11.8 A
11 kW (14.8 hp)36.1 A21.8 A20.8 A17.3 A
15 kW (20.1 hp)49.2 A29.8 A28.3 A23.6 A
22 kW (29.5 hp)72.2 A43.7 A41.5 A34.6 A
30 kW (40.2 hp)98.4 A59.6 A56.6 A47.2 A
37 kW (49.6 hp)121.4 A73.5 A69.8 A58.2 A
45 kW (60.3 hp)147.7 A89.4 A84.9 A70.8 A
55 kW (73.8 hp)180.5 A109.2 A103.8 A86.5 A
75 kW (100.6 hp)246.1 A149.0 A141.5 A117.9 A

Frequently asked questions

How do I calculate the current of a three-phase motor?

I = P × 1000 / (√3 × U × cos φ × η). For an 11 kW motor at 400 V with cos φ 0.85 and 90% efficiency: 11,000 / (1.732 × 400 × 0.85 × 0.9) = 20.8 A.

What size breaker do I need for a motor?

At least 125% of the full-load current, rounded up to the next standard size. Motors with heavy starting loads may need a motor-protection or inverse-time breaker set up to 250% of full-load current.

What cable size do I need?

Size the copper cable for 125% of the full-load current using your local code tables, then check voltage drop over the cable length (keep it below 3–5%). Long runs often need a larger cable than current alone suggests.

What power supply does a press brake need?

Hydraulic press brakes of 40–300 t typically have 5.5–30 kW main motors plus controls; servo-electric press brakes draw less. Use the machine’s total connected power in this calculator to size the supply.

Reviewed by the HARSLE engineering team · Last updated October 2026. Results are engineering estimates; confirm critical values with your machine and tooling documentation.

Full-load current—